Plastic Tank with Lid
1 - Mechanical Installation
The required IoT Pro BSP Adapter with Flange for this installation can be ordered from the IoT Pro Product Selector, under Radar & Tilt Module Accessories > Mechanical Adapter Selection
General Idea

Threaded Attachment
If the threaded attachment was not delivered pre-assembled, follow this guide to assemble it onto the device.
Mounting Procedure
Where possible, mount the device on a fixed part of the tank rather than on the lid. This avoids having to remove or disturb the device whenever the tank needs to be opened for inspection or maintenance.
Identify a suitable mounting area on the tank, close enough to the lid to allow any debris produced during drilling to be collected and removed
Drill a 50mm diameter hole at the selected location using a suitable hole saw (add MPN)
Centre the supplied flange over the drilled hole and secure it using the five self-drilling screws (add MPN). Tighten the screws progressively in a star pattern to ensure even pressure.
Note: If the tank wall is too thick for the supplied self-drilling screws, suitable bolts and nuts may be used instead.
Note: If the mounting surface is uneven or the flange does not sit flush, apply a suitable sealant (add MPN) to ensure a proper seal.
Screw the device's threaded attachment onto the flange until securely seated. Tighten securely, but do not apply excessive force.
Required Measurements
Take the following measurements based on whether the plastic tank is a cuboid, horizontal cylinder or vertical cylinder.

2 - System Commissioning
Device Setup
Activate the IoT Pro device according to the communication network being used:
Platform Setup
Make sure that you have access to the IoT Pro Cloud Platform. Follow the Getting Started guide to familiarize yourself first.
Open the IoT Pro Dashboard Mobile Application and log in
Navigate to Assets and select Create Asset
Under Asset Name & Device:
Enter an Asset Name
Select Application:
20_IOTPRO-RadarDistanceAirTiltSelect Device: choose the device installed in the previous section
Assign the asset to a group, if required
Complete the Asset Information fields as required
Under Asset Images, use Take Photo to capture the required photos of the completed installation
Under Advanced Fields, configure the following:
Bottom Offset (cm): 0
Chimney Height (cm): add flange chimney height
Asset Shape: Horizontal Cylinder, Vertical Cylinder or Cuboid and enter the measurements taken during installation
Supply/Discharge
Discharge for sewage, wastewater, or similar applications
Supply for water, diesel, fuel, or similar applications
Click Create Asset
Open the IoT Pro Device Setup Mobile Application, reconnect to the installed device, and select Send Message to transmit a new reading
Return to the IoT Pro Dashboard Mobile Application and navigate to Live Map to view your Asset
Use the Level Supply or Level Discharge Dashboard to view the circuit's readings and trends