Diesel Tank Management Installation
top-level wiring diagram like generator in case it’s straightforward for others? 230VAC, 12VDC, 24VDC diagrams - add shortcut links
1 - Configuration Selection
Select the configuration options that best match the installation requirements. The IoT Pro Diesel Tank Management system can be configured with different power supply, barcode scanner, and fuel level sensor options.
Power Supply
The system can be configured for 230VAC, 12VDC, or 24VDC operation.
230VAC is typically used for fixed fuel dispensing installations.
12VDC and 24VDC are typically used for portable fuel dispensing systems.
The system supply voltage must match the pump supply voltage. For example, a system using a 12VDC pump must also be configured for a 12VDC supply.
Barcode Scanner
The system supports either a Wired Barcode Scanner or Wireless Barcode Scanner.
The wired barcode scanner is supplied with a 5m cable and is generally the preferred option where the dispensing point can be conveniently reached. The wireless barcode scanner provides greater freedom of movement but has a few additional considerations:
The scanner can be misplaced or removed from the dispensing area
The scanner must be correctly placed in its charging cradle to ensure that it remains charged
Fuel Level Sensor
Two fuel level sensor options are available:
Submersible Pressure Sensor - Recommended for fixed fuel tank installations
Capacitive Level Sensor - Recommended for portable or mobile fuel tank installations
2 - Mechanical Installation
Main Panel Installation
Install the main panel close to the existing diesel fuel dispensing equipment to minimize cable lengths, while keeping the panel easily accessible for operation and maintenance.
When selecting the installation location:
Ensure sufficient space is available around the panel for access and cable routing
Allow additional space for the Wired Barcode Scanner holder or Wireless Barcode Scanner enclosure
If the panel is exposed to rain, install a suitable rainwater deflector (paraqua) above the enclosure
2 x Image: Wired and wireless barcode systems installed (show bolts or wall anchors inside)
Image: Rainwater deflector (paraqua)
Mount the main panel securely using suitable fixings for the installation surface:
Wall mounting: For typical installations, use four 6 x 45 mm wall plugs
Metal panel or structure: Use four M6 A2 stainless-steel bolts, washers and nuts
Cable Management
Route all field wiring to the main panel using one of the following methods:
Surface wiring: Use the cable glands at the bottom of the main panel where the cables are routed externally along the wall
Concealed wiring: Alternatively, drill an internal cable entry hole to bring the wiring directly into the rear or inside of the panel. This provides a neater installation and reduces the risk of cable tampering.
In both cases, use split flexible conduit where multiple cables follow the same route to keep the incoming wiring grouped, protected, and neatly organized.
image: vassallo for a mix of both
image: wall wiring (callus garden centre, piscopo)
image: hole inside panel for concealed wiring (tec + split conduit showing)
Barcode Scanner Installation
Wireless Barcode Scanner
Mount the wireless barcode scanner enclosure next to the main panel, using:
Wall mounting: For typical installations, use four 6 x 45 mm wall plugs
Metal panel or structure: Use four M6 A2 stainless-steel bolts, washers and nuts
Connect the DC barrel connector and RJ50 cable to the back of the wireless scanner. Secure the scanner holder inside the enclosure using its two mounting holes and suitable fixings.
Insert the battery into the bottom of the wireless barcode scanner
Select the preferred cable routing method:
Surface wiring: Install suitable cable glands at the bottom of the scanner enclosure. Route the DC power cable and RJ50 cable through the fifth and sixth cable glands of the main panel, respectively.
Concealed wiring: Drill a suitable cable entry hole to route the cables internally between the scanner enclosure and the main panel
image: wireless enclosure installed
image: cable gland wiring or concealed wiring hole (tec) - add labels
Wired Barcode Scanner
Install the barcode scanner holder in a convenient location next to or below the main panel, using:
Wall mounting: For typical installations, use two 6 x 45 mm wall plugs
Metal panel or structure: Use two M6 A2 stainless-steel bolts, washers and nuts
Route the scanner cable into the main panel through the fifth cable gland, ensuring that the gland is properly tightened
Place the barcode scanner in its holder
image: holder installed
image: wired barcode scanner inside holder
Pulser Installation
Apply a suitable pipe sealant to all threaded fittings. Würth Pipe Sealant, Art. No. 0893 577 050, is recommended. Always allow the sealant to cure before pressurizing the system.
Install the pulser as the last fitting before the dispensing pipe. The supplied pulser uses 1" BSP threaded connections. Select the appropriate fittings for the installation.
image: common 1" BSP fittings - male-to-male and male-to-hose-tail (labelled)
Ensure that the pulser is installed in the correct flow direction, as indicated by the arrow on its body
image: Pulser showing the flow direction
Route the pulser cable to the main panel. If an extension is required, use a suitable junction box with a 3-core, 0.5 mm² cable. Where cable glands are used, route the cable through the third gland from the left.
image: typical installation
Fuel Level Sensor Installation
Capacitive Level Sensor
The Capacitive Level Sensor is recommended for moving, portable fuel tanks
Choose the appropriate mounting method:
BSP adapter: When a suitable threaded port is available
Flange: When no suitable threaded port is available add which self-drill screws to use
refer to generator for more in-depth installation guide?
The required fittings for these installations can be ordered from the IoT Pro Product Selector, under IoT Pro Diesel Tank Module > Diesel Tank Module Accessories > Mechanical Adapter Selection.
image: vassallo portable tank installation
Cut the sensor probe to approximately 3 mm shorter than the internal tank depth. Calibrate the sensor using the supplied calibration tool.
Route the sensor cable to the main panel. If an extension is required, use a suitable junction box with a 3-core, 0.5 mm² cable. Where cable glands are used, route the cable through the fourth gland from the left.
Submersible Pressure Sensor
The Submersible Pressure Sensor is recommended for fixed, on-ground fuel tanks
Choose the appropriate mounting method:
BSP adapter: When a suitable threaded port is available
Flange: When no suitable threaded port is available add which self-drill screws to use
See Diesel and Water Tank Installation for a more in-depth installation guide
The required fittings for these installations can be ordered from the IoT Pro Product Selector, under IoT Pro Level Submersible Module > Submersible Module Accessories > Mechanical Adapter Selection.
Lower the sensor to the bottom of the tank, then raise it approximately 5cm to prevent contact with sediment. Secure the cable gland to hold the sensor in position.
Route the sensor cable to the main panel. If an extension is required, use a suitable junction box with a 3-core, 0.5mm² cable. Where cable glands are used, route the cable through the fourth gland from the left.
Where additional cable protection is required, use split flexible conduit and secure it with self-amalgamating tape.
image: vassallo and tec/piscopo/callus for typical installation
The submersible pressure sensor requires atmospheric pressure reference for accurate measurements. If a junction box is used, a 1-2mm hole may be drilled at the gland’s side or at the bottom of the enclosure (to protect opening from water ingress).
The submersible pressure sensor uses a blue wire for the GND connection
3 - Electrical Installation
Disconnect both the main system and pump power supplies before proceeding. Verify that all circuits are de-energized. Electrical installation must only be performed by a qualified electrician or authorized technician.
Refer to DIN-Rail Terminal Block Wiring for a better understanding of DIN numbering
link to refer to appendix for full wiring diagrams
Peripheral Wiring
Following the Mechanical Installation, the following peripheral cables should be routed into the main panel and ready for connection:
Barcode Scanner: One cable for the wired scanner, or two cables (DC power and RJ50) for the wireless scanner
Pulser: 3-core cable
Fuel Level Sensor: Cable from either the submersible pressure sensor or the capacitive level sensor
Connect each peripheral as described below, keeping the system and pump power supplies disconnected throughout the installation.
Barcode Scanner
Both barcode scanner configurations use the same communication and ground connections:
Connect the Orange and Brown wires to Left Group/Yellow (terminal 7) and Left Group/Green (terminal 8), respectively
Connect the Black wire to GND (terminal 6)
Connect the Red supply wire according to the scanner configuration:
Wired Barcode Scanner: 5VDC (terminal 5)
Wireless Barcode Scanner: 12VDC (terminal 1 or 2)
Pulser
Connect the Red wire to 12 VDC (terminal 1 or 2)
Connect the Black wire to GND (terminal 3 or 4)
Connect the Yellow wire to Left Group/White - Pulse Input (terminal 10)
Fuel Level Sensor
Both fuel level sensor configurations use the same supply and signal connections:
Connect the Red wire to 12VDC (terminal 1 or 2)
Connect the ground wire to GND (terminal 3 or 4)
Connect the Yellow wire to Right Group/Grey – Fuel Level Input (terminal 14)
The ground wire differs between sensors:
Submersible Pressure Sensor: Blue wire
Capacitive Level Sensor: Black wire
Route the analogue fuel level sensor cable away from other electrical wiring, particularly power cables, to minimise electrical interference and ensure accurate, stable readings
Power Supply and Pump Connection
As outlined in Configuration Selection, the system supports 230VAC, 12VDC and 24VDC configurations.
12VDC - Conversion Method
add loom video with captions
24VDC - Conversion Method
add loom video with captions
230VAC - Standard Configuration
Connect the incoming mains supply and pump cables to the 6-way terminal block as illustrated below.

4 - System Commissioning
to continue
Ensure all connections are securely terminated and verified before restoring power. Power on the system and check that the barcode scanner lights up or beeps.
Device Setup
Connect to the IoT Pro device using the mobile application
Confirm that Peripherals is OK
Activate the IoT Pro device according to the communication network being used:
Platform Setup
Setup Asset etc.
Send Message
Verification
Dispense fuel
Check report
5 - Appendix
DIN-Rail Terminal Block Wiring
Connections are referred to left-to-right as seen when panel is open
Terminal Position | Internal (Top) Wire | Function | Connect To |
|---|---|---|---|
1-2 | Red | 12V x 2 | Submersible Pressure, Pulser, Capacitive Sensor, Wireless Barcode Scanner |
3-4 | Black | GND x 2 | |
5 | Red | 5V | Wired Barcode Scanner |
6 | Black | GND | |
7 | Left Group / Yellow | RS232 TX | Barcode Scanner (Orange) |
8 | Left Group / Green | RS232 RX | Barcode Scanner (Brown) |
9 | Left Group / Grey | DIN1: RFID/iButton 1-Wire | |
10 | Left Group / White | DIN2: Pulse Input | Pulser (Yellow) |
11 | Left Group / Brown | DIN3: Manual Override | |
12 | Right Group / Yellow | N/A | |
13 | Right Group / Green | N/A | |
14 | Right Group / Grey | AIN1: Fuel Level | Submersible Pressure or Capacitive Sensor (Yellow) |
15 | Right Group / White | OUT1: Pump Relay | |
16 | Right Group / Brown | OUT2: Buzzer |
Peripherals Specifications
Wired Barcode Scanner
Power Supply: 5VDC
Wiring
Red Wire: +5V
Black Wire: GND
Orange Wire: RS232 RX
Brown Wire: RS232 TX
Submersible Pressure Sensor
Power Supply: 10-30VDC
Wiring
Red Wire: +V
Yellow Wire: Analogue Output
Blue Wire: GND
Pulser
Power Supply: 5-24 VDC
Wiring
Red Wire: +V
Yellow Wire: Pulse Output
Black Wire: GND
Wireless Barcode Scanner
Power Supply: 12VDC
Wiring
Red Wire: +12VDC
Black Wire: GND
Orange Wire: RS232 RX
Brown Wire: RS232 TX
Capacitive Level Sensor
Power Supply: 10-32 VDC
Wiring
Red Wire: +V
Yellow Wire: Analogue Output
Black Wire: GND