Circuit Monitoring Installation

1 - Electrical Connections

Electrical Preparation

This installation must be performed by a qualified electrician or authorized technician only due to high voltage hazards

  • DIN rail mounting is recommended for both the power supply and relays

  • 2-core 0.75 mm² wiring can be used for the AC supply, DC output and relay connections

  1. Locate the 230 VAC supply or electrical distribution board

  2. Isolate the electrical supply and verify that it is de-energized

  3. Install the 230VAC/12VDC power supply (PSR-01512) to power the IOTPRO

  4. Identify the circuit to be monitored, typically at the circuit breaker output

  5. Install the relay socket (GZM80) and relay (RM85-2011-25-5230). Connect the relay coil terminals as follows:

    • A1: Circuit breaker output (L)

    • A2: Corresponding Neutral (N) from the distribution board

  6. Repeat steps 4–5 for each additional circuit to be monitored, up to a maximum of 6 circuits

IOTPRO Wiring

Refer to IoT Pro Opening and Closing for instructions on opening the device to access its wiring connections.

Refer to the wiring diagram below and complete the following steps:

  1. Route the 12VDC power supply connections through the first cable gland. Connect the positive (+12V) and negative (GND) wires to the corresponding IOTPRO power terminals.

  2. Connect each relay's dry contacts to the corresponding IOTPRO digital input:

    • Terminal 11 (COM): Connect to DIN1–DIN6, respectively

    • Terminal 14 (NO): Connect to IOTPRO GND

  3. Verify all electrical connections, secure and conceal the wiring, tighten the cable glands and securely close the IOTPRO enclosure. Once the installation has been checked, the electrical supply can be safely re-energized.

Use an 8-core, 0.25 mm² cable, such as LAPP UNITRONIC LiYY (MPN: 0028308), to simplify wiring between the IOTPRO and the six relays. Allocate six conductors to DIN1–DIN6 and the remaining two to the shared GND connections, distributing them between the relays as required.


2 - Mechanical Installation

Refer to IoT Pro Installation Options for different installation options. Wall anchors are recommended for most applications.


3 - System Commissioning

Device Setup

Activate the IoT Pro device according to the communication network being used:

  1. Activate the Device - Cellular

Platform Setup

Make sure that you have access to the IoT Pro Cloud Platform. Follow the Getting Started guide to familiarize yourself first.

  1. Open the IoT Pro Dashboard Mobile Application and log in

  2. Navigate to Assets and select Create Asset

  3. Under Asset Name & Device:

    1. Enter an Asset Name

    2. Select Application: 4_IOTPRO-DigitalAnalogueSerial

    3. Select Device: choose the device installed in the previous section

    4. Assign the asset to a group, if required

  4. Complete the Asset Information fields as required

  5. Under Asset Images, use Take Photo to capture the required photos of the completed installation

  6. Under Advanced Fields, configure the following:

    1. Asset Type: Circuit

    2. Invert Values: Disabled

    3. Channel Setting: DIN1 to DIN6 correspond to Channels 1 to 6, respectively

  7. Click Create Asset

  8. Open the IoT Pro Device Setup Mobile Application, reconnect to the installed device, and select Send Message to transmit a new reading

  9. Return to the IoT Pro Dashboard Mobile Application and navigate to Live Map to view your Asset

  10. Use the Detect Clear Dashboard to view the circuit's readings and trends