16_IOTPRO-ColdStorageTemp
Fields
Field Name | ID - HEX | Size in Bytes | Description | Data Type | Uplink/ Downlink/ Both |
|---|---|---|---|---|---|
telemetry_param_temperature_channel_1 | 0x0FBF | 2 | Temperature from an External Probe | Signed Integer (/100), Unit: °C | Uplink |
telemetry_param_temperature_channel_2 | 0x0FC0 | 2 | Temperature from an External Probe | Signed Integer (/100), Unit: °C | Uplink |
telemetry_param_dry_contact_channel_1 | 0x0802 | 1 | State of DIN1 | Boolean (0: Open, 1: Closed) | Uplink |
telemetry_param_dry_contact_channel_2 | 0x0803 | 1 | State of DIN2 | Boolean (0: Open, 1: Closed) | Uplink |
Example Packet
Packet (HEX) | 0x36B20140E17D77FD5D0FAA00101F42685D16260FBFFFFD0FC0F0010802010803000FA240AF1F42685D168D0FBFFA010FC00A120802000803010FA240AF | |
ID1 | 0x36B2 | IMEI |
Value1 | 0x0140E17D77FD5D | 352812193545565 |
ID2 | 0x0FAA | Application ID |
Value2 | 0x0010 | Cold Storage Temperature |
ID3 | 0x1F42 | Event 1: UNIX Time |
Value3 | 0x685D1626 | 1750930982 |
ID4 | 0x0FBF | Event 1: Temperature Channel 1 |
Value4 | 0xFFFD | -0.03°C |
ID5 | 0x0FC0 | Event 1: Temperature Channel 2 |
Value5 | 0xF001 | -40.95°C |
iD6 | 0x0802 | Event 1: Dry Contact Channel 1 |
Value6 | 0x01 | Closed |
ID7 | 0x0803 | Event 1: Dry Contact Channel 2 |
Value7 | 0x00 | Open |
ID8 | 0x0FA2 | Event 1: Power Supply Voltage |
Value8 | 0x40AF | 16.559V |
ID9 | 0x1F42 | Event 2: UNIX Time |
Value9 | 0x685D168D | 1750931085 |
ID10 | 0x0FBF | Event 2: Temperature Channel 1 |
Value10 | 0xFA01 | -15.35°C |
ID11 | 0x0FC0 | Event 2: Temperature Channel 2 |
Value11 | 0x0A12 | 25.78°C |
ID12 | 0x0802 | Event 2: Dry Contact Channel 1 |
Value12 | 0x00 | Open |
ID13 | 0x0803 | Event 2: Dry Contact Channel 2 |
Value13 | 0x01 | Closed |
ID14 | 0x0FA2 | Event 2: Power Supply Voltage |
Value14 | 0x40AF | 16.559V |