15_IOTPRO-EnergyMonitoringRS485

Fields

Field Name

ID - HEX

Size in Bytes

Description

Data Type

Uplink/

Downlink/

Both

telemetry_param_ac_current_channel_1

0x1773

3

RMS AC Current for Channel 1

Signed Integer (/1000), Unit: A

Uplink

telemetry_param_ac_current_channel_2

0x1774

3

RMS AC Current for Channel 2

Signed Integer (/1000), Unit: A

Uplink

telemetry_param_ac_current_channel_3

0x1775

3

RMS AC Current for Channel 3

Signed Integer (/1000), Unit: A

Uplink

telemetry_param_ac_voltage_line_neutral_channel_1

0x0FDC

2

RMS AC Voltage from Line to Neutral for Channel 1

Unsigned Integer (/100), Unit: V

Uplink

telemetry_param_ac_voltage_line_neutral_channel_2

0x0FDD

2

RMS AC Voltage from Line to Neutral for Channel 2

Unsigned Integer (/100), Unit: V

Uplink

telemetry_param_ac_voltage_line_neutral_channel_3

0x0FDE

2

RMS AC Voltage from Line to Neutral for Channel 3

Unsigned Integer (/100), Unit: V

Uplink

telemetry_param_ac_power_active_channel_1

0x1778

3

Active AC Power for Channel 1

Signed Integer, Unit: W

Uplink

telemetry_param_ac_power_active_channel_2

0x1779

3

Active AC Power for Channel 2

Signed Integer, Unit: W

Uplink

telemetry_param_ac_power_active_channel_3

0x177A

3

Active AC Power for Channel 3

Signed Integer, Unit: W

Uplink

telemetry_param_ac_energy_total_forward_active_channel_1

0x1F54

4

Forward Active AC Energy total for Channel 1

Unsigned Integer (/10), Unit: kWh

Uplink

telemetry_param_ac_energy_total_forward_active_channel_2

0x1F55

4

Forward Active AC Energy total for Channel 2

Unsigned Integer (/10), Unit: kWh

Uplink

telemetry_param_ac_energy_total_forward_active_channel_3

0x1F56

4

Forward Active AC Energy total for Channel 3

Unsigned Integer (/10), Unit: kWh

Uplink

telemetry_param_ac_power_factor_channel_1

0x0FD7

2

Power Factor for Channel 1

Signed Integer (/1000), Unit: N/A

Uplink

telemetry_param_ac_power_factor_channel_2

0x0FD8

2

Power Factor for Channel 2

Signed Integer (/1000), Unit: N/A

Uplink

telemetry_param_ac_power_factor_channel_3

0x0FD9

2

Power Factor for Channel 3

Signed Integer (/1000), Unit: N/A

Uplink

telemetry_param_ac_frequency

0x0FE0

2

Frequency of Channel 1

Unsigned Integer (/100), Unit: Hz

Uplink

telemetry_param_ac_voltage_harmonic_distortion_channel_1

0x0FE5

2

Voltage THD+N for Channel 1

Unsigned Integer (/100), Unit: %

Uplink

telemetry_param_ac_voltage_harmonic_distortion_channel_2

0x0FE6

2

Voltage THD+N for Channel 2

Unsigned Integer (/100), Unit: %

Uplink

telemetry_param_ac_voltage_harmonic_distortion_channel_3

0x0FE7

2

Voltage THD+N for Channel 3

Unsigned Integer (/100), Unit: %

Uplink

telemetry_param_ac_current_harmonic_distortion_channel_1

0x0FE9

2

Current THD+N for Channel 1

Unsigned Integer (/100), Unit: %

Uplink

telemetry_param_ac_current_harmonic_distortion_channel_2

0x0FEA

2

Current THD+N for Channel 2

Unsigned Integer (/100), Unit: %

Uplink

telemetry_param_ac_current_harmonic_distortion_channel_3

0x0FEB

2

Current THD+N for Channel 3

Unsigned Integer (/100), Unit: %

Uplink

Example Packet

Packet (HEX)

0x36B20140E17D77FD5D0FAA000D1F42685D16261773000FA017740007D017750003E80FDC08FC0FDD09080FDE090F1778000BB817790003E8177A0001F41F54000027101F55000027101F56000027100FD703E80FD803D00FD903C80FE013880FE505DC0FE605E00FE705E80FE901F40FEA01F80FEB01FC

ID1

0x36B2

IMEI

Value1

0x0140E17D77FD5D

352812193545565

ID2

0x0FAA

Application ID

Value2

0x000F

Energy Meter (RS485)

ID3

0x1F42

Event 1: UNIX Time

Value3

0x685D1626

1750930982

ID4

0x1773

Event 1: RMS AC Current for Channel 1

Value4

0x000FA0

4.000A

ID5

0x1774

Event 1: RMS AC Current for Channel 2

Value5

0x0007D0

2.000A

ID6

0x1775

Event 1: RMS AC Current for Channel 3

Value6

0x0003E8

1.000A

ID7

0x0FDC

Event 1: RMS AC Voltage from Line to Neutral for Channel 1

Value7

0x08FC

230.0V

ID8

0x0FDD

Event 1: RMS AC Voltage from Line to Neutral for Channel 2

Value8

0x0908

231.2V

ID9

0x0FDE

Event 1: RMS AC Voltage from Line to Neutral for Channel 3

Value9

0x090F

231.9V

ID10

0x1778

Event 1: Active AC Power for Channel 1

Value10

0x000BB8

3000W

ID11

0x1779

Event 1: Active AC Power for Channel 2

Value11

0x0003E8

1000W

ID12

0x177A

Event 1: Active AC Power for Channel 3

Value12

0x0001F4

500W

ID13

0x1F54

Event 1: Forward Active AC Energy total for Channel 1

Value13

0x00002710

1000.0kWh

ID14

0x1F55

Event 1: Forward Active AC Energy total for Channel 2

Value14

0x00002710

1000.0kWh

ID15

0x1F56

Event 1: Forward Active AC Energy total for Channel 3

Value15

0x00002710

1000.0kWh

ID16

0x0FD7

Event 1: Power Factor for Channel 1

Value16

0x03E8

1.000

ID17

0x0FD8

Event 1: Power Factor for Channel 2

Value17

0x03D0

0.976

ID18

0x0FD9

Event 1: Power Factor for Channel 3

Value18

0x03C8

0.968

ID19

0x0FE0

Event 1: Frequency of Channel 1

Value19

0x1388

50.00Hz

ID20

0x0FE5

Event 1: Voltage THD+N for Channel 1

Value20

0x05DC

15.00%

ID21

0x0FE6

Event 1: Voltage THD+N for Channel 2

Value21

0x05E0

15.04%

ID22

0x0FE7

Event 1: Voltage THD+N for Channel 3

Value22

0x05E8

15.12%

ID23

0x0FE9

Event 1: Current THD+N for Channel 1

Value23

0x01F4

5.00%

ID24

0x0FEA

Event 1: Current THD+N for Channel 2

Value24

0x01F8

5.04%

ID25

0x0FEB

Event 1: Current THD+N for Channel 3

Value25

0x01FC

5.08%